# apcupsd.conf(5)

apcupsd(8) configuration file

## NAME

**apcupsd.conf** – [apcupsd(8)](/apcupsd/8.md) configuration file

## DESCRIPTION

**apcupsd.conf** is the configuration file for the [apcupsd(8)](/apcupsd/8.md) program.  The file is a plain ASCII text file which comprises a number  of configuration directives which control how the apcupsd program behaves when controlling most American Power Conversion Corp (APC) UPSes. The configuration file is also used for the  [apctest(8)](/apctest/8.md) program when bulk programming the EEPROM in a Smart-UPS model.

It will almost certainly be necessary to customise the information  in the configuration file to suit your particular configuration and  operating requirements.

*Note* *that* *the* *apcupsd* *daemon* *must* *be* *restarted* *in* *order* *for* *changes* *to* *the* *configuration* *file* *to* *become* *active.*

The configuration file directives are explained in the subsections below.

### GENERAL CONFIGURATION DIRECTIVES

- UPSNAME \<string\>

  Specify a name for the UPS for log files, status reports etc.

- UPSCABLE \[ simple \| smart \| ether \| usb \| 940-0119A \| 940-0127A \| 940-0128A \| 940-0020B \| 940-0020C \| 940-0023A \| 940-0024B \| 940-0024C \| 940-1524C \| 940-0024G \| 940-0095A \| 940-0095B \| 940-0095C \| 940-0625A \| MAM-04-02-2000 \]

  The type of cable used to connect the UPS to the computer.

- UPSTYPE \[ dumb \| apcsmart \| net \| usb \| snmp \| pcnet \| modbus \|test \]

  The type of APC UPS that you have.

- DEVICE \<name\>

  The name of the device used for communication between the UPS and the computer. For a USB UPS, you should leave the DEVICE  directive blank and apcupsd will figure out where the device is  located.

  - apcsmart : /dev/tty\*\* (serial connection)

  - usb : leave blank! (USB connection)

  - net : hostname:port (NIS connection)

  - snmp : hostname:port:vendor:community (SNMP connection)

  - dumb : /dev/tty\*\* (serial connection)

  - pcnet : ipaddr:username:passphrase (AP9617 SmartSlot card)

  - modbus : /dev/tty\*\* (serial connection)

  - modbus : leave blank (USB connection)

    If you have problems, please see the apcupsd manual for more  detailed information and comprehensive troubleshooting advice.

- POLLTIME \<seconds\>

  The rate in seconds that the daemon polls the UPS for status. This rate is automatically set to 1 second when the UPS goes on battery and reset to the specified value when the utility power returns. This  setting applies both to directly-attached UPSes and networked UPSes.  A low setting will improve the daemon's responsiveness to certain events at the cost of higher CPU utilisation. The default of 60 is appropriate  for most situations.

- LOCKFILE \<path\>

  apcupsd creates a lockfile for the serial or USB port in the specified  directory.  It must be changed when running more than one copy of apcupsd  on the same computer to control multiple UPSes.

- SCRIPTDIR \<path\>

  Directory in which apccontrol and event scripts are located.  Defaults to */usr/local/etc/apcupsd*. It must be changed when running more than one copy of apcupsd  on the same computer to control multiple UPSes.

- PWRFAILDIR \<path\>

  Directory in which apcupsd writes the powerfail flag file created when apcupsd initiates a system shutdown. The directory  is checked in halt scripts to determine if turning off the  UPS output power is required.  Defaults to */var/run*. It must be changed when running more than one copy of apcupsd  on the same computer to control multiple UPSes.

- NOLOGINDIR \<path\>

  Directory in which apcupsd writes the nologin file which tells  the OS to disallow new logins. Defaults to */var/run*. It must be changed when running more than one copy of apcupsd  on the same computer to control multiple UPSes.

### NIS CONFIGURATION DIRECTIVES

- NETSERVER \[ on \| off \]

  Turns the network information server (NIS) on or off. When on,  apcupsd serves status and event information over the network.  This information is also used by the web-based CGI monitoring  programs. The default is set to on.

- NISIP \<IP address\>

  Specifies the IP address of the network interface on which apcupsd will listen for incoming connections. The default value is  0.0.0.0 which means the NIS will listen for connections on all network  interfaces. If the computer has more than one interface, you can specify the IP of a single interface to limit connections to that interface.  Specifying the loopback address (127.0.0.1) will cause the NIS daemon to  accept connections only from the local computer.

- NISPORT \<port\>

  Specifies the port to be used by the NIS daemon. The default is 3551 which has been received from IANA as the official apcupsd networking port.  It must be changed when running more than one copy of apcupsd  on the same computer to control multiple UPSes.

- EVENTSFILE \<filename\>

  If you want NIS to provide the last 10 events via the network, you must  specify a file where apcupsd will save these events. The default is: */var/log/apcupsd.events*. apcupsd will save at most the last 50 events to this file. When more than  50 events are saved and a network request for the events arrives, apcupsd  will truncate the file to the most recent 10 events. It must be changed when running more than one copy of apcupsd  on the same computer to control multiple UPSes.

### LOGGING CONFIGURATION DIRECTIVES

- STATTIME \<seconds\>

  Specifies the time interval between writes to the status file. If set  to zero, the status file will not be written. The status file will  disappear in a future  apcupsd version as its functionality has been  replaced by the Network Information Server and the [apcaccess(8)](/apcaccess/8.md) program.

- STATFILE \<file\>

  Specifies the file to be used when writing the status information.  The default is  */etc/apcupsd/apcupsd.status*. It must be changed when running more than one copy of apcupsd  on the same computer to control multiple UPSes.

- LOGSTATS \[ on \| off \]

  Activate log file. This generates a lot of output, so if you turn  this on, be sure that the file defined in  [syslog.conf(5)](/syslog.conf/5.md) for LOG\_NOTICE is a named pipe.

- DATATIME \<seconds\>

  Specifies the time interval between writes of the APC PowerChute  software-like data information to the log file.

- FACILITY \<log-facility\>

  Change the system logging (syslog) facility. The default is daemon. This parameter can be useful if you wish to direct the apcupsd system logging information to other than your system default files.  See [syslog.conf(5)](/syslog.conf/5.md) for details of other possible facilities and general system logging  configuration.

### POWER FAILURE CONFIGURATION DIRECTIVES

- ONBATTERYDELAY \<seconds\>

  The number of seconds from when a power failure is detected until apcupsd reacts with an onbattery event.

- BATTERYLEVEL \<percentage\>

  apcupsd will shutdown the system during a power failure when  the remaining battery charge falls below the specified percentage.  The default is 5.

- MINUTES \<minutes\>

  apcupsd will shutdown the system during a power failure when the  remaining runtime on batteries as internally calculated by the UPS  falls below the specified minutes. The default is 3.

- TIMEOUT \<seconds\>

  After a power failure occurs,  apcupsd will shutdown the system after the specified number of seconds  have expired.  For a Smart-UPS, this should normally be set to zero so  that the shutdown time will be determined by the battery level or  remaining runtime (see above). This command is, however, useful for  a Back-UPS or other simple signalling UPS which does not report  battery level or the remaining runtime. It is also useful for testing  apcupsd because you can force a rapid shutdown by setting a small  value (eg 60) and turning off the power to the UPS.

  TIMEOUT, BATTERYLEVEL, and MINUTES can all be set without problems.  apcupsd will initiate a shutdown when the first of these conditions becomes valid.

- ANNOY \<seconds\>

  Specifies the time in seconds between broadcast messages requesting logged in users to log off from the system. This timer starts only when the UPS is running on battery. The default is 300 seconds (5 minutes).

- ANNOYDELAY \<seconds\>

  Specifies the delay time in seconds before broadcast messages requesting logged in users to log off from the system. This timer starts only after the UPS is running on battery power. This timer is reset when  the power returns. The default is 60 seconds (ie the first request to  log off occurs after 60 seconds on battery power).

- NOLOGON \[ disable \| timeout \| percent \| minutes \| always \]

  Specifies when apcupsd should create the nologon file to prevent users from logging on to the system.

  "disable" prevents apcupsd from creating the nologin file.

  "timeout" specifies a specific wait time before apcupsd creates the nologin file.

  "percent" specifies the percentage of battery charge remaining before apcupsd creates the nologin file.

  "minutes" specifies the battery runtime remaining before  apcupsd creates the nologin file.

  "always" specifies that apcupsd should create the nologin file immediately after  a power failure occurs.

  This directive is important for allowing systems with BIG UPSes  to run normally until the system administrator determines the  need for dumping users.  It also allows the system administrator  to hold the "ANNOY" factor until the  */etc/nologin* file is created.

- KILLDELAY \<seconds\>

  Specifies the number of seconds for which apcupsd will continue running after a shutdown has been requested. After  the specified time, apcupsd will attempt to put the UPS into  hibernate mode and kill the power to the computer. This is for  use on operating systems where apcupsd cannot regain control after a  shutdown (eg FreeBSD) to issue an apcupsd --killpower command. Setting  the delay to 0 disables it.

### SHARE-UPS CONFIGURATION DIRECTIVES

- UPSCLASS \[ standalone \| shareslave \| sharemaster \]

  The default is "standalone" and should be used for  all computers powered by the UPS,  with a direct connection to  the UPS and where there are no other computers dependent on power  from the UPS. This is the "normal" case.

  Use "shareslave" if you are using a Share-UPS interface expander  and connected to the BASIC port (simple signalling).

  Use "sharemaster", if you are using a Share-UPS interface expander and connected to the ADVANCED port (smart signalling).

- UPSMODE \[ disable \| share \]

  Set to "disable" for normal standalone operation to indicate that  you are disabling the Share-UPS interface expander support.

  Set to "share" for two to seven additional simple signalling ports on a Share-UPS interface expander. This code may not be fully tested in every new release.

### APCTEST EEPROM CONFIGURATION DIRECTIVES

These directives have no effect on the operation of  [apcupsd(8)](/apcupsd/8.md) but are reserved for use by [apctest(8)](/apctest/8.md) when bulk programming the values of the UPS EEPROM configuration variables  in a Smart-UPS model.

- UPSNAME \<string\>

  Name of UPS. Maximum of 8 characters.

- BATTDATE \[ mm/dd/yy \| dd/mm/yy \]

  Last battery replacement date. Maximum of 8 characters.

- SENSITIVITY \[ H \| M \| L \]

  -

    H : High (most sensitive setting)

  -

    M : Medium

  -

    L : Low (least sensitive setting)

- WAKEUP \[ 000 \| 060 \| 180 \| 300 \]

  The time delay in seconds that the UPS waits after the return of utility  power before "waking up" and restoring power to the connected equipment.

- SLEEP \[ 020 \| 180 \| 300 \| 600 \]

  The time delay in seconds for which the UPS waits or "sleeps" after  it receives a request to power off the connected system.

- LOTRANSFER \<voltage\>

  Low line voltage causing transfer to battery power or activation of SmartBoost. Allowable values depend on the last letter of the firmware or APCMODEL. Typical values are:

    D  106  103  100  097\
     M  177  172  168  182\
     A  092  090  088  086\
     I  208  204  200  196

  where D = domestic (USA), M = Canada, A = Asia and I = International.

- HITRANSFER \<voltage\>

  High line voltage causing transfer to battery power or activation of SmartTrim. Allowable values depend on the last letter of the firmware or APCMODEL. Typical values are:

    D  127  130  133  136\
     M  229  234  239  224\
     A  108  110  112  114\
     I  253  257  261  265

  where D = domestic (USA), M = Canada, A = Asia and I = International.

- RETURNCHARGE \[ 00 \| 15 \| 50 \| 90 \]

  Percentage of battery charge needed for the UPS to restore power to the  connected equipment.

- BEEPSTATE \[ 0 \| T \| L \| N \]

  Alarm delay.

  -

    0 : Zero delay after power fails.

  -

    T : When power fails plus 30 seconds.

  -

    L : When low battery occurs.

  -

    N : Never.

- LOWBATT \<minutes\>

  Low battery warning occurs when the specified number of minutes remains before the UPS estimates battery power will be exhausted. There are four  user-changeable settings: 2, 5, 7, or 10 minutes

- OUTPUTVOLTS \<voltage\>

  UPS nominal output voltage when running on battery. Allowable values depend on the last letter of the firmware or APCMODEL. Typical values are:

    D  115\
     M  208\
     A  100\
     I  230  240  220  225

  where D = domestic (USA), M = Canada, A = Asia and I = International.

- SELFTEST \[ 336 \| 168 \| ON \| OFF \]

  Self test interval in hours (336 = 2 weeks, 168 = 1 week,  ON = at power on, OFF = never).

## EXAMPLES

Note that in the following examples, the device names assume that you are using Linux. Device names for serial devices in \*BSD and other operating systems will be different.

### Minimal USB Configuration for a USB UPS

     UPSCABLE usb\
      UPSTYPE usb\
      DEVICE\
      LOCKFILE /var/lock\
      UPSCLASS standalone\
      UPSMODE disable

Notice no device name is specified.  [apcupsd(8)](/apcupsd/8.md) will try all the well known USB ports. Only specify a specific  USB device name if you know what you are doing. For detailed information on setting up a USB UPS, refer to the "USB Configuration" section of the apcupsd manual.

### Minimal Serial Configuration for a Smart UPS

     UPSCABLE smart\
      UPSTYPE apcsmart\
      DEVICE /dev/ttyS0\
      LOCKFILE /var/lock\
      UPSCLASS standalone\
      UPSMODE disable

Normally there would be more configuration directives to  completely customise your installation, but this example shows  the minimum required.

### Minimal Serial Configuration for a Dumb UPS

     UPSCABLE \<number of the cable used\>\
      UPSTYPE dumb\
      DEVICE /dev/ttyS0\
      LOCKFILE /var/lock\
      UPSCLASS standalone\
      UPSMODE disable

If your cable does not have low battery detection (eg such  cables include the APC 940-0020B and 940-0023A), you will also  need to define the TIMEOUT \<seconds\> configuration directive to set  the number of seconds on battery during a power failure after which  apcupsd will do a system shutdown.

Normally there would be more configuration directives to  completely customise your installation, but this example shows  the minimum required.

## FILES

*/etc/apcupsd/apcupsd.conf* default configuration file

## SEE ALSO

[syslog.conf(5)](/syslog.conf/5.md), [apcupsd(8)](/apcupsd/8.md), [apctest(8)](/apctest/8.md).

The HTML apcupsd manual installed on your system or available online at http://www.apcupsd.org/

## AUTHORS

Trevor Roydhouse (current) Andre M. Hedrick Christopher J. Reimer