# apctest(8)

apcupsd(8) test program

## NAME

**apctest** – [apcupsd(8)](/apcupsd/8.md) test program

## SYNOPSIS

**apctest**

## DESCRIPTION

**apctest** is a program that enables the running of certain low-level tests to  check the operation of the attached simple signalling American Power Conversion Corp (APC) UPS and to check that your  [apcupsd(8)](/apcupsd/8.md) configuration is correctly setup and can establish communication with  the UPS.

For an APC UPS operating in APC smart protocol mode, **apctest** enables the reading and programming of the values of the UPS EEPROM  configuration variables as well and the performing of a battery  runtime calibration. It also  provides a simple TTY chat mode which  allows direct interaction with the UPS via the APC smart protocol.  For details of this protocol and the available commands, refer to the  detailed "APC Smart Protocol" section in the apcupsd manual.

IMPORTANT: Before running **apctest**

- Check that the UPSCABLE, UPSTYPE and DEVICE configuration directives in the [apcupsd.conf(5)](/apcupsd.conf/5.md) configuration file have been set appropriately; and

- Shutdown apcupsd if it is running. You cannot run both apcupsd and **apctest** at the same time.

When run, **apctest** displays a menu of options which are different depending on  whether the UPS is connected to a USB port or to  a serial port. For a serial port connection, there are two different menus depending on whether the UPS is operating in  APC smart protocol mode or simple signalling mode - this also depends on  which cable is used to connect to the UPS. If a simple signalling  cable is used to connect to a Smart-UPS, the UPS will only be able  to operate in simple signalling mode.

**apctest** saves a transcript of the session to the file  *apctest.out* in the directory from which the program was called. Its content is  useful for debugging purposes.

## USB PORT

When using a UPS connected to a USB port (eg Back-UPS RS 1500),  the following menu options will appear:

### Option 1) Test kill UPS power

Performs a power down of the UPS into hibernate mode.

### Option 2) Perform self-test

Performs an immediate self-test (switches to battery power to do so).

### Option 3) Read last self-test result

Displays the last self-test result.

### Option 4) View/Change battery date

Displays the current battery replacement date and optionally allows you to change it - useful when the battery  is replaced so that you can accurately keep track of its age.

### Option 5) View manufacturing date

Displays the date the UPS was manufactured.

### Option 6) View/Change alarm behavior

Sets the delay period before the UPS starts sounding its alarm  when the utility power is lost.

### Option 7) View/Change sensitivity

Changes how sensitive the UPS is to the utility power quality and  voltage fluctuations - (H)igh, (M)edium or (L)ow. The higher the  sensitivity, the faster the UPS will switch to battery power or  activate SmartBoost/SmartTrim (features that avoid using battery power provided the under/over voltage is within 12% of nominal).  This setting should normally be set to High unless the UPS switches  to battery power frequently, in which case a less sensitive setting  will preserve UPS batteries... if the connected equipment can tolerate the power quality.

### Option 8) View/Change low transfer voltage

Sets the low voltage level at which the UPS switches to battery or  activates SmartBoost.

### Option 9) View/Change high transfer voltage

Sets the high voltage level at which the UPS switches to battery or  activates SmartTrim.

### Option 10) Perform battery calibration

This performs a battery runtime calibration. This can only be performed if your battery is charged to 100% of capacity.  The runtime calibration discharges the UPS battery to  approximately 25% of capacity. The exact percentage depends on  the UPS model.

The advantage of doing this calibration is that the UPS will recalibrate the remaining runtime counter that it maintains and therefore report a more accurate estimated runtime. As batteries age, they tend to hold less charge, so the UPS's internal runtime counter may not be accurate after several years.

It is recommended that battery runtime calibration be performed annually. Performing it too often shortens the lifetime of the UPS batteries.

### Option 11) Test Alarm

This option will cause the UPS alarm beeper to sound for several seconds.

### Option 12) View/Change self-test interval

This option allows you to change the time interval between automatic UPS self-tests.

### Option Q) Quit

Exits from the program.

## SERIAL PORT (SMART PROTOCOL MODE)

When using a UPS operating in APC smart protocol mode (eg a Smart-UPS) the following menu options will appear:

### Option 1) Query the UPS for all known values

Selecting this option probes the UPS for all EEPROM configuration variable values known  to **apctest** and displays them in rather raw format. This output  can be useful for providing technical support if you are having  problems with the behaviour of the UPS or  [apcupsd(8)](/apcupsd/8.md).

### Option 2) Perform a Battery Runtime Calibration

This performs a battery runtime calibration. This can only be performed if your battery is charged to 100% of capacity.  The runtime calibration discharges the UPS battery to  approximately 25% of capacity. The exact percentage depends on  the UPS model. **apctest** can optionally abort the calibration if it detects that the  battery charge is below 10%.

The advantage of doing this calibration is that the UPS will recalibrate the remaining runtime counter that it maintains and therefore report a more accurate estimated runtime. As batteries age, they tend to hold less charge, so the UPS's internal runtime counter may not be accurate after several years.

It is recommended that battery runtime calibration be performed annually. Performing it too often shortens the lifetime of the UPS batteries.

### Option 3) Abort Battery Calibration

This option aborts an in progress battery runtime calibration.

### Option 4) Monitor Battery Calibration progress

Allows restarting of the monitoring of a battery runtime calibration.

### Option 5) Program EEPROM

Allows the programming of the values of a Smart-UPS's EEPROM configuration variables.

Choosing this option presents a sub-menu of programming  options which are detailed below.

- Option 1) Print EEPROM values

  Prints the value of all EEPROM configuration variables known to **apctest**.

- Option 2) Change Battery date

  Changes the battery date - useful when the battery  is replaced so that you can accurately keep track of its age.

- Option 3) Change UPS name

  Changes the UPS name - use no more than 8 characters to name the UPS.

- Option 4) Change sensitivity

  Changes how sensitive the UPS is to the utility power quality and  voltage fluctuations - (H)igh, (M)edium or (L)ow. The higher the  sensitivity, the faster the UPS will switch to battery power or  activate SmartBoost/SmartTrim (features that avoid using battery power provided the under/over voltage is within 12% of nominal).  This setting should normally be set to High unless the UPS switches  to battery power frequently, in which case a less sensitive setting  will preserve UPS batteries... if the connected equipment can tolerate the power quality.

- Option 5) Change alarm delay

  Changes the delay period before the UPS starts sounding its alarm when the utility power is lost.

- Option 6) Change low battery warning delay

  Changes the remaining runtime minutes at which the UPS will send the  low battery signal. When the UPS internally calculates that the specified  number of minutes remains before battery power will be exhausted, it sends  the low battery warning.

- Option 7) Change wakeup delay

  Changes the delay before the UPS restores power to connected equipment when the utility power returns after shutting down in hibernate mode.

- Option 8) Change shutdown delay

  Changes the delay for which the UPS waits before shutting off power to the connected equipment after being commanded to power down in hibernate mode.

- Option 9) Change low transfer voltage

  Changes the low voltage level at which the UPS switches to battery or  activates SmartBoost.

- Option 10) Change high transfer voltage

  Changes the high voltage level at which the UPS switches to battery or  activates SmartTrim.

- Option 11) Change battery return threshold percent

  Changes the battery charge percentage required after power down in  hibernate mode before to the UPS will restore power to connected  equipment on the return of utility power.

- Option 12) Change output voltage when on batteries

  Changes the nominal voltage output when the UPS is running on battery  power.

- Option 13) Change the self test interval

  Changes or disables the automatic self-test interval.

- Option 14) Set EEPROM with configuration file values

  This option allows the bulk programming of the EEPROM configuration variables from the values contained in the  */etc/apcupsd.conf* configuration file.  Refer to the "APCTEST EEPROM CONFIGURATION DIRECTIVES" section of the man page for [apcupsd.conf(5)](/apcupsd.conf/5.md)

- Option 15) Quit

  This option exits back to the previous (main) menu.

### Option 6) Enter TTY mode communicating with UPS

This option allows direct interaction with the attached UPS using the APC smart protocol commands.

WARNING: Take special care what commands you enter because it is possible to cause the UPS to suddenly shutdown or, in the  worst case, modify the UPS in such a way as to permanently disable  it. Do NOT experiment with unknown or unsupported commands. Caveat Utilitor!

### Option 7) Quit

Exits from the program.

## SERIAL PORT (SIMPLE SIGNALLING MODE)

When using an APC UPS operating in simple signalling mode the following menu options will appear:

### Option 1) Test 1 - normal mode

The test result depends on the model of UPS and type of cable being  used. Refer to the "Using apctest on Serial-Line UPSses" section in the apcupsd manual for details.

### Option 2) Test 2 - no cable

The test result depends on the model of UPS and type of cable being  used. Refer to the "Using apctest on Serial-Line UPSses" section in the apcupsd manual for details.

### Option 3) Test 3 - no power

The test result depends on the model of UPS and type of cable being  used. Refer to the "Using apctest on Serial-Line UPSses" section in the apcupsd manual for details.

### Option 4) Test 4 - low battery (requires Test 3 first)

The test result depends on the model of UPS and type of cable being  used. Refer to the "Using apctest on Serial-Line UPSses" section in the apcupsd manual for details.

### Option 5) Test 5 - battery exhausted

The test result depends on the model of UPS and type of cable being  used. Refer to the "Using apctest on Serial-Line UPSses" section in the apcupsd manual for details.

### Option 6) Test 6 - kill UPS power

The test result depends on the model of UPS and type of cable being  used. Refer to the "Using apctest on Serial-Line UPSses" section in the apcupsd manual for details.

### Option 7) Test 7 - run tests 1 through 5

This option has  **apctest** guess which cable should be used with the attached UPS.

### Option 9) Quit

Exits from the program.

## FILES

*/etc/apcupsd/apcupsd.conf* default configuration file

*apctest.out* transcript of the  **apctest** session

## SEE ALSO

[apcupsd.conf(5)](/apcupsd.conf/5.md), [apcupsd(8)](/apcupsd/8.md).

The HTML apcupsd manual installed on your system or available online at http://www.apcupsd.org/